Filtered by vendor Schneider-electric
Subscriptions
Total
765 CVE
CVE | Vendors | Products | Updated | CVSS v3.1 |
---|---|---|---|---|
CVE-2022-41669 | 1 Schneider-electric | 2 Ecostruxure Operator Terminal Expert, Pro-face Blue | 2025-05-02 | 7 High |
A CWE-347: Improper Verification of Cryptographic Signature vulnerability exists in the SGIUtility component that allows adversaries with local user privileges to load a malicious DLL which could result in execution of malicious code. Affected Products: EcoStruxure Operator Terminal Expert(V3.3 Hotfix 1 or prior), Pro-face BLUE(V3.3 Hotfix1 or prior). | ||||
CVE-2022-41668 | 1 Schneider-electric | 2 Ecostruxure Operator Terminal Expert, Pro-face Blue | 2025-05-02 | 7 High |
A CWE-704: Incorrect Project Conversion vulnerability exists that allows adversaries with local user privileges to load a project file from an adversary-controlled network share which could result in execution of malicious code. Affected Products: EcoStruxure Operator Terminal Expert(V3.3 Hotfix 1 or prior), Pro-face BLUE(V3.3 Hotfix1 or prior). | ||||
CVE-2022-41667 | 1 Schneider-electric | 2 Ecostruxure Operator Terminal Expert, Pro-face Blue | 2025-05-02 | 7 High |
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists that allows adversaries with local user privileges to load a malicious DLL which could lead to execution of malicious code. Affected Products: EcoStruxure Operator Terminal Expert(V3.3 Hotfix 1 or prior), Pro-face BLUE(V3.3 Hotfix1 or prior). | ||||
CVE-2022-41666 | 1 Schneider-electric | 2 Ecostruxure Operator Terminal Expert, Pro-face Blue | 2025-05-02 | 7 High |
A CWE-347: Improper Verification of Cryptographic Signature vulnerability exists that allows adversaries with local user privileges to load a malicious DLL which could lead to execution of malicious code. Affected Products: EcoStruxure Operator Terminal Expert(V3.3 Hotfix 1 or prior), Pro-face BLUE(V3.3 Hotfix1 or prior). | ||||
CVE-2022-41671 | 1 Schneider-electric | 2 Ecostruxure Operator Terminal Expert, Pro-face Blue | 2025-05-01 | 7 High |
A CWE-89: Improper Neutralization of Special Elements used in SQL Command (‘SQL Injection’) vulnerability exists that allows adversaries with local user privileges to craft a malicious SQL query and execute as part of project migration which could result in execution of malicious code. Affected Products: EcoStruxure Operator Terminal Expert(V3.3 Hotfix 1 or prior), Pro-face BLUE(V3.3 Hotfix1 or prior). | ||||
CVE-2022-41670 | 1 Schneider-electric | 2 Ecostruxure Operator Terminal Expert, Pro-face Blue | 2025-04-30 | 7 High |
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists in the SGIUtility component that allows adversaries with local user privileges to load malicious DLL which could result in execution of malicious code. Affected Products: EcoStruxure Operator Terminal Expert(V3.3 Hotfix 1 or prior), Pro-face BLUE(V3.3 Hotfix1 or prior). | ||||
CVE-2022-0222 | 1 Schneider-electric | 28 Modicon M340 Bmxnoe0100, Modicon M340 Bmxnoe0100 Firmware, Modicon M340 Bmxnoe0110 and 25 more | 2025-04-29 | 7.5 High |
A CWE-269: Improper Privilege Management vulnerability exists that could cause a denial of service of the Ethernet communication of the controller when sending a specific request over SNMP. Affected products: Modicon M340 CPUs(BMXP34* versions prior to V3.40), Modicon M340 X80 Ethernet Communication modules:BMXNOE0100 (H), BMXNOE0110 (H), BMXNOR0200H RTU(BMXNOE* all versions)(BMXNOR* versions prior to v1.7 IR24) | ||||
CVE-2022-37301 | 1 Schneider-electric | 96 Modicon M340 Bmx P34-2010, Modicon M340 Bmx P34-2010 Firmware, Modicon M340 Bmx P34-2030 and 93 more | 2025-04-28 | 7.5 High |
A CWE-191: Integer Underflow (Wrap or Wraparound) vulnerability exists that could cause a denial of service of the controller due to memory access violations when using the Modbus TCP protocol. Affected products: Modicon M340 CPU (part numbers BMXP34*)(V3.40 and prior), Modicon M580 CPU (part numbers BMEP* and BMEH*)(V3.22 and prior), Legacy Modicon Quantum/Premium(All Versions), Modicon Momentum MDI (171CBU*)(All Versions), Modicon MC80 (BMKC80)(V1.7 and prior) | ||||
CVE-2017-9961 | 1 Schneider-electric | 1 Pro-face Gp Pro Ex | 2025-04-20 | N/A |
A vulnerability exists in Schneider Electric's Pro-Face GP Pro EX version 4.07.000 that allows an attacker to execute arbitrary code. Malicious code installation requires an access to the computer. By placing a specific DLL/OCX file, an attacker is able to force the process to load arbitrary DLL and execute arbitrary code in the context of the process. | ||||
CVE-2017-7907 | 1 Schneider-electric | 1 Wonderware Historian Client | 2025-04-20 | N/A |
An Improper XML Parser Configuration issue was discovered in Schneider Electric Wonderware Historian Client 2014 R2 SP1 and prior. An improperly restricted XML parser (with improper restriction of XML external entity reference, or XXE) may allow an attacker to enter malicious input through the application which could cause a denial of service or disclose file contents from a server or connected network. | ||||
CVE-2017-7967 | 1 Schneider-electric | 1 Vampset | 2025-04-20 | N/A |
All versions of VAMPSET software produced by Schneider Electric, prior to V2.2.189, are susceptible to a memory corruption vulnerability when a corrupted vf2 file is used. This vulnerability causes the software to halt or not start when trying to open the corrupted file. This vulnerability occurs when fill settings are intentionally malformed and is opened in a standalone state, without connection to a protection relay. This attack is not considered to be remotely exploitable. This vulnerability has no effect on the operation of the protection relay to which VAMPSET is connected. As Windows operating system remains operational and VAMPSET responds, it is able to be shut down through its normal closing protocol. | ||||
CVE-2017-7969 | 1 Schneider-electric | 3 Citect Anywhere, Powerscada Anywhere, Powerscada Expert | 2025-04-20 | N/A |
A cross-site request forgery vulnerability exists on the Secure Gateway component of Schneider Electric's PowerSCADA Anywhere v1.0 redistributed with PowerSCADA Expert v8.1 and PowerSCADA Expert v8.2 and Citect Anywhere version 1.0 for multiple state-changing requests. This type of attack requires some level of social engineering in order to get a legitimate user to click on or access a malicious link/site containing the CSRF attack. | ||||
CVE-2017-6017 | 1 Schneider-electric | 30 Bmxnoc0401, Bmxnoc0401 Firmware, Bmxnoe0100 and 27 more | 2025-04-20 | N/A |
A Resource Exhaustion issue was discovered in Schneider Electric Modicon M340 PLC BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP341000, BMXP342000, BMXP3420102, BMXP3420102CL, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, and BMXP342030H. A remote attacker could send a specially crafted set of packets to the PLC causing it to freeze, requiring the operator to physically press the reset button on the PLC in order to recover. | ||||
CVE-2017-6030 | 1 Schneider-electric | 6 Modicon M221, Modicon M221 Firmware, Modicon M241 and 3 more | 2025-04-20 | 6.5 Medium |
A Predictable Value Range from Previous Values issue was discovered in Schneider Electric Modicon PLCs Modicon M221, firmware versions prior to Version 1.5.0.0, Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The affected products generate insufficiently random TCP initial sequence numbers that may allow an attacker to predict the numbers from previous values. This may allow an attacker to spoof or disrupt TCP connections. | ||||
CVE-2017-13997 | 1 Schneider-electric | 2 Wonderware Indusoft Web Studio, Wonderware Intouch | 2025-04-20 | N/A |
A Missing Authentication for Critical Function issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 or prior, and InTouch Machine Edition v8.0 SP2 or prior. InduSoft Web Studio provides the capability for an HMI client to trigger script execution on the server for the purposes of performing customized calculations or actions. A remote malicious entity could bypass the server authentication and trigger the execution of an arbitrary command. The command is executed under high privileges and could lead to a complete compromise of the server. | ||||
CVE-2017-14024 | 1 Schneider-electric | 2 Wonderware Indusoft Web Studio, Wonderware Intouch | 2025-04-20 | N/A |
A Stack-based Buffer Overflow issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 Patch 1 and prior versions, and InTouch Machine Edition v8.0 SP2 Patch 1 and prior versions. The stack-based buffer overflow vulnerability has been identified, which may allow remote code execution with high privileges. | ||||
CVE-2016-5815 | 1 Schneider-electric | 6 Ion5000, Ion7300, Ion7500 and 3 more | 2025-04-20 | N/A |
An issue was discovered on Schneider Electric IONXXXX series power meters ION73XX series, ION75XX series, ION76XX series, ION8650 series, ION8800 series, and PM5XXX series. No authentication is configured by default. An unauthorized user can access the device management portal and make configuration changes. | ||||
CVE-2016-8367 | 1 Schneider-electric | 16 Magelis Gto Advanced Optimum Panel, Magelis Gto Advanced Optimum Panel Firmware, Magelis Gtu Universal Panel and 13 more | 2025-04-20 | 5.3 Medium |
An issue was discovered in Schneider Electric Magelis HMI Magelis GTO Advanced Optimum Panels, all versions, Magelis GTU Universal Panel, all versions, Magelis STO5xx and STU Small panels, all versions, Magelis XBT GH Advanced Hand-held Panels, all versions, Magelis XBT GK Advanced Touchscreen Panels with Keyboard, all versions, Magelis XBT GT Advanced Touchscreen Panels, all versions, and Magelis XBT GTW Advanced Open Touchscreen Panels (Windows XPe). An attacker can open multiple connections to a targeted web server and keep connections open preventing new connections from being made, rendering the web server unavailable during an attack. | ||||
CVE-2016-8354 | 1 Schneider-electric | 1 Unity Pro | 2025-04-20 | N/A |
An issue was discovered in Schneider Electric Unity PRO prior to V11.1. Unity projects can be compiled as x86 instructions and loaded onto the PLC Simulator delivered with Unity PRO. These x86 instructions are subsequently executed directly by the simulator. A specially crafted patched Unity project file can make the simulator execute malicious code by redirecting the control flow of these instructions. | ||||
CVE-2017-9956 | 1 Schneider-electric | 1 U.motion Builder | 2025-04-20 | N/A |
An authentication bypass vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which the system contains a hard-coded valid session. An attacker can use that session ID as part of the HTTP cookie of a web request, resulting in authentication bypass |