Filtered by vendor Rockwellautomation
Subscriptions
Total
301 CVE
CVE | Vendors | Products | Updated | CVSS v3.1 |
---|---|---|---|---|
CVE-2012-4695 | 1 Rockwellautomation | 1 Rslinx Enterprise | 2025-04-11 | N/A |
LogReceiver.exe in Rockwell Automation RSLinx Enterprise CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 allows remote attackers to cause a denial of service (service outage) via a zero-byte UDP packet that is not properly handled by Logger.dll. | ||||
CVE-2012-4713 | 1 Rockwellautomation | 1 Factorytalk Services Platform | 2025-04-11 | N/A |
Integer signedness error in RNADiagnostics.dll in Rockwell Automation FactoryTalk Services Platform (FTSP) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 allows remote attackers to cause a denial of service (service outage or RNADiagReceiver.exe daemon crash) via UDP data that specifies a negative integer value. | ||||
CVE-2012-4714 | 1 Rockwellautomation | 1 Factorytalk Services Platform | 2025-04-11 | N/A |
Integer overflow in RNADiagnostics.dll in Rockwell Automation FactoryTalk Services Platform (FTSP) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 allows remote attackers to cause a denial of service (service outage or RNADiagReceiver.exe daemon crash) via UDP data that specifies a large integer value. | ||||
CVE-2012-4715 | 1 Rockwellautomation | 1 Rslinx Enterprise | 2025-04-11 | N/A |
Buffer overflow in LogReceiver.exe in Rockwell Automation RSLinx Enterprise CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 allows remote attackers to cause a denial of service (daemon crash) or possibly execute arbitrary code via a UDP packet with a certain integer length value that is (1) too large or (2) too small, leading to improper handling by Logger.dll. | ||||
CVE-2012-0221 | 1 Rockwellautomation | 2 Factorytalk, Rslogix 5000 | 2025-04-11 | N/A |
The FactoryTalk (FT) RNADiagReceiver service in Rockwell Automation Allen-Bradley FactoryTalk CPR9 through SR5 and RSLogix 5000 17 through 20 does not properly handle the return value from an unspecified function, which allows remote attackers to cause a denial of service (service outage) via a crafted packet. | ||||
CVE-2011-3489 | 1 Rockwellautomation | 1 Rslogix | 2025-04-11 | N/A |
RnaUtility.dll in RsvcHost.exe 2.30.0.23 in Rockwell RSLogix 19 and earlier allows remote attackers to cause a denial of service (crash) via a crafted rna packet with a long string to TCP port 4446 that triggers (1) "a memset zero overflow" or (2) an out-of-bounds read, related to improper handling of a 32-bit size field. | ||||
CVE-2011-2957 | 1 Rockwellautomation | 1 Factorytalk Diagnostics Viewer | 2025-04-11 | N/A |
Unspecified vulnerability in Rockwell Automation FactoryTalk Diagnostics Viewer before V2.30.00 (CPR9 SR3) allows local users to execute arbitrary code via a crafted FactoryTalk Diagnostics Viewer (.ftd) configuration file, which triggers memory corruption. | ||||
CVE-2011-2530 | 1 Rockwellautomation | 2 Eds Hardware Installation Tool, Rslinx | 2025-04-11 | N/A |
Buffer overflow in RSEds.dll in RSHWare.exe in the EDS Hardware Installation Tool 1.0.5.1 and earlier in Rockwell Automation RSLinx Classic before 2.58 allows user-assisted remote attackers to cause a denial of service (application crash) or possibly execute arbitrary code via a malformed .eds file. | ||||
CVE-2010-2965 | 2 Rockwellautomation, Windriver | 3 1756-enbt\/a, 1756-enbt\/a Firmware, Vxworks | 2025-04-11 | N/A |
The WDB target agent debug service in Wind River VxWorks 6.x, 5.x, and earlier, as used on the Rockwell Automation 1756-ENBT series A with firmware 3.2.6 and 3.6.1 and other products, allows remote attackers to read or modify arbitrary memory locations, perform function calls, or manage tasks via requests to UDP port 17185, a related issue to CVE-2005-3804. | ||||
CVE-2009-3739 | 1 Rockwellautomation | 2 Ab Micrologix Controller 1100, Ab Micrologix Controller 1400 | 2025-04-11 | N/A |
Multiple unspecified vulnerabilities on the Rockwell Automation AB Micrologix 1100 and 1400 controllers allow remote attackers to obtain privileged access or cause a denial of service (halt) via unknown vectors. | ||||
CVE-2014-0755 | 1 Rockwellautomation | 2 Logix 5000 Controller, Rslogix 5000 Design And Configuration Software | 2025-04-11 | N/A |
Rockwell Automation RSLogix 5000 7 through 20.01, and 21.0, does not properly implement password protection for .ACD files (aka project files), which allows local users to obtain sensitive information or modify data via unspecified vectors. | ||||
CVE-2012-6435 | 1 Rockwellautomation | 17 1756-enbt, 1756-eweb, 1768-enbt and 14 more | 2025-04-11 | N/A |
Rockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400 allow remote attackers to cause a denial of service (control and communication outage) via a CIP message that specifies a logic-execution stop and fault. | ||||
CVE-2012-6437 | 1 Rockwellautomation | 17 1756-enbt, 1756-eweb, 1768-enbt and 14 more | 2025-04-11 | N/A |
Rockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400 do not properly perform authentication for Ethernet firmware updates, which allows remote attackers to execute arbitrary code via a Trojan horse update image. | ||||
CVE-2012-6438 | 1 Rockwellautomation | 17 1756-enbt, 1756-eweb, 1768-enbt and 14 more | 2025-04-11 | N/A |
Buffer overflow in Rockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400 allows remote attackers to cause a denial of service (NIC crash and communication outage) via a malformed CIP packet. | ||||
CVE-2012-6441 | 1 Rockwellautomation | 17 1756-enbt, 1756-eweb, 1768-enbt and 14 more | 2025-04-11 | N/A |
Rockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400 allow remote attackers to obtain sensitive information via a crafted CIP packet. | ||||
CVE-2022-3156 | 1 Rockwellautomation | 1 Studio 5000 Logix Emulate | 2025-04-10 | 7.8 High |
A remote code execution vulnerability exists in Rockwell Automation Studio 5000 Logix Emulate software. Users are granted elevated permissions on certain product services when the software is installed. Due to this misconfiguration, a malicious user could potentially achieve remote code execution on the targeted software. | ||||
CVE-2009-0474 | 1 Rockwellautomation | 1 Controllogix 1756-enbt\/a Ethernet\/ Ip Bridge | 2025-04-09 | N/A |
The web interface in the Rockwell Automation ControlLogix 1756-ENBT/A EtherNet/IP Bridge Module allows remote attackers to obtain "internal web page information" and "internal information about the module" via unspecified vectors. NOTE: this may overlap CVE-2002-1603. | ||||
CVE-2009-0472 | 1 Rockwellautomation | 1 Controllogix 1756-enbt\/a Ethernet\/ Ip Bridge | 2025-04-09 | N/A |
Multiple cross-site scripting (XSS) vulnerabilities in the web interface in the Rockwell Automation ControlLogix 1756-ENBT/A EtherNet/IP Bridge Module allow remote attackers to inject arbitrary web script or HTML via unspecified vectors. | ||||
CVE-2009-0473 | 1 Rockwellautomation | 1 Controllogix 1756-enbt\/a Ethernet\/ Ip Bridge | 2025-04-09 | N/A |
Open redirect vulnerability in the web interface in the Rockwell Automation ControlLogix 1756-ENBT/A EtherNet/IP Bridge Module allows remote attackers to redirect users to arbitrary web sites and conduct phishing attacks via unspecified vectors. | ||||
CVE-2024-12672 | 2 Microsoft, Rockwellautomation | 2 Windows, Arena | 2025-04-03 | 7.3 High |
A third-party vulnerability exists in the Rockwell Automation Arena® that could allow a threat actor to write beyond the boundaries of allocated memory in a DOE file. If exploited, a threat actor could leverage this vulnerability to execute arbitrary code. To exploit this vulnerability, a legitimate user must execute the malicious code crafted by the threat actor. |